HVAC Design for Pharmaceutical
Facilities
In pharmaceutical
manufacturing, how space conditions impact the product being made is of primary
importance. The pharmaceutical facilities are closely supervised by the U.S.
food and drug administration (FDA), which requires manufacturing companies to
conform to cGMP (current Good Manufacturing Practices). These regulations,
which have the force of law, require that manufacturers, processors, and
packagers of drugs to take proactive steps to ensure that their products are
safe, pure, and effective. GMP regulations require a quality approach to
manufacturing, enabling companies to minimize or eliminate instances of
contamination, mix ups, and errors.
The GMP for HVAC services embraces number of issues
starting with the selection of building materials and finishes, the flow of
equipment, personnel and products, determination of key parameters like
temperature, humidity, pressures, filtration, airflow parameters and classification
of cleanrooms. It also governs the level of control of various parameters for
quality assurance, regulating the acceptance criteria, validation of the
facility, and documentation for operation and maintenance.
Various countries have formulated their own GMPs. In the
United States, it is regulated by several documents such as Federal Standard
209, code of Federal regulations CFR 210 & 211 etc, which are revised and
updated from time to time. The European Community has a "Guide to Good
Manufacturing Practice for Medicinal Products” and in the United Kingdom it is
BS 5295. The World Health Organization (WHO) version of GMP is used by
pharmaceutical regulators and the pharmaceutical industry in over one hundred
countries worldwide, primarily in the developing world. In some countries, the
GMP follows largely the country of the principal technology provider. All GMP’s
have one common theme……
“CLEANLINESS, CLEANLINESS and CLEANLINESS”
What can HVAC do?
HVAC system performs four basic functions:
1. Control airborne
particles, dust and micro-organisms – Thru air filtration using high efficiency
particulate air (HEPA) filters.
2. Maintain room pressure
(delta P) – Areas that must remain “cleaner” than surrounding areas must be
kept under a “positive” pressurization, meaning that air flow must be from the
“cleaner” area towards the adjoining space (through doors or other
openings) to reduce the chance of airborne contamination. This is achieved by
the HVAC system providing more air into the “cleaner” space than is
mechanically removed from that same space.
3. Maintain space moisture
(Relative Humidity) – Humidity is controlled by cooling air to dew point
temperatures or by using desiccant dehumidifiers. Humidity can affect the
efficacy and stability of drugs and is sometimes important to effectively mould
the tablets.
4. Maintain space
temperature - Temperature can affect production directly or indirectly by
fostering the growth of microbial contaminants on workers.
Each of above parameter is controlled and evaluated
in light of its potential to impact product quality.
What HVAC can’t do?
1. HVAC can not clean up
the surfaces of a contaminated surfaces, room or equipment
2. HVAC can not compensate
for workers who do not follow procedures
We will learn about the
specific design aspects later in this course, but first we will briefly discuss
the generic pharmaceutical process.
Pharmaceutical Process
The task of the pharmaceutical manufacturer
is to combine the medicinally active agents provided by a fine chemicals plant,
or by extraction from vegetable, animal or other source, with suitable inactive
ingredients so that the end product may be used in the correct dosage to
produce the effect needed.
Simplified Process
Figure below illustrates a simplified diagram of the
chemical synthesis process for pharmaceuticals. There are five primary stages
in chemical synthesis: (1) reaction, (2) separation, (3) crystallization, (4)
purification, and (5) drying. Each of these five stages is described below.
Reaction(s)
–
In the reaction process,
raw materials are fed into a reactor vessel, where reactions such as
alkylations, hydrogenations, or brominations are performed. The most common
type of reactor vessel is the kettle-type reactor generally made of stainless
steel or glass-lined carbon steel, range from 50 to several thousand gallons in
capacity. The reactors may be heated or cooled, and reactions may be performed
at atmospheric pressure, at elevated pressure, or in a vacuum. Generally, both
reaction temperature and pressure are monitored and controlled. Nitrogen may be
required for purging the reactor, and some intermediates may be recycled back
into the feed. Some reactions are aided via mixing action provided by an
agitator. A condenser system may be required to control vent losses. Reactors
are often attached to pollution control devices to remove volatile organics or
other compounds from vented gases.
Separation
–
The main types of separation processes are
extraction, decanting, centrifugation, and filtration. The extraction process
is used to separate liquid mixtures.
Extraction process is used to separate liquid mixtures. It takes advantage of
the differences in the solubility of mixture components i.e. a solvent that
preferentially combines with only one of the mixture components is added to the
mixture. Two streams result from this process: the extract, which is the
solvent-rich solution containing the desired mixture component, and the
raffinate, which is the residual feed solution containing the non-desired
mixture component(s).
Decanting is a simple process that removes liquids from insoluble solids
that have settled to the bottom of a reactor or settling vessel. The liquid is
either pumped out of the vessel or poured from the vessel, leaving only the solid
and a small amount of liquid in the vessel.
Centrifugation is a process that removes solids from a liquid stream using the
principle of centrifugal force. A liquid-solid mixture is added to a rotating
vessel—or centrifuge—and an outward force pushes the liquid through a filter
that retains the solid phase. The solids are manually scraped off the sides of
the vessel or with an internal scraper. To avoid air infiltration, centrifuges
are usually operated under a nitrogen atmosphere and kept sealed during operation.
Filtration separates fluid/solid mixtures by flowing fluid through a porous
media, which filters out the solid particulates. Batch filtration systems
widely used by the pharmaceutical industry include plate and frame filters,
cartridge filters, nutsche filters, and filter/dryer combinations.
Crystallization
Crystallization is a widely used separation
technique that is often used alone or in combination with one or more of the
separation processes described above. Crystallization refers to the formation
of solid crystals from a supersaturated solution. The most common methods of
super saturation in practice are cooling, solvent evaporation, and chemical
reaction. The solute that has crystallized is subsequently removed from the
solution by centrifugation or filtration.
Purification
Purification
follows separation, and typically uses the separation methods described above.
Several steps are often required to achieve the desired purity level.
Re-crystallization is a common technique
employed in purification. Another common approach is washing with additional
solvents, followed by filtration.
Drying
The final step
in chemical synthesis is drying the product (or intermediates). Drying is done
by evaporating solvents from solids. Solvents are then condensed for reuse or
disposal. The pharmaceutical industry uses several different types of dryers,
including tray dryers, rotary dryers, drum or tumble dryers, or pressure filter
dryers. Prior to 1980, the most common type of dryer used by the pharmaceutical
industry was the vacuum tray dryer.
Today, however, the most common dryers are
tumble dryers or combination filter/dryers. In the combination filter/dryer,
input slurry is first filtered into a cake, after which a hot gaseous medium is
blown up through the filter cake until the desired level of dryness is
achieved. Tumble dryers typically range in capacity from 20 to 100 gallons. In
tumble dryers, a rotating conical shell enhances solvent evaporation while
blending the contents of the dryer. Tumble dryers utilize hot air circulation
or a vacuum combined with conduction from heated surfaces.
Product
Extraction
Active ingredients that are extracted from
natural sources are often present in very low concentrations. The volume of
finished product is often an order of magnitude smaller than the raw materials,
making product extraction an inherently expensive process.
Precipitation, purification, and solvent
extraction methods are used to recover active ingredients in the extraction
process. Solubility can be changed by pH adjustment, by salt formation, or by
the addition of an anti-solvent to isolate desired components in precipitation.
Solvents can be used to remove active
ingredients from solid components like plant or animal tissues, or to remove
fats and oils from the desired product. Ammonia is often used in natural
extraction as a means of controlling pH.
Fermentation
In fermentation, microorganisms are typically
introduced into a liquid to produce pharmaceuticals as by-products of normal microorganism
metabolism. The fermentation process is typically controlled at a particular
temperature and pH level under a set of aerobic or anaerobic conditions that are
conducive to rapid microorganism growth. The process involves three main steps:
(i) seed preparation, (ii) fermentation, and (iii) product recovery.
Seed
preparation
The fermentation process begins with seed
preparation, where inoculum (medium containing microorganisms) is produced in
small batches within seed tanks. Seed tanks are typically 1-10% of the size of
production fermentation tanks (U.S. EPA 1997).
Fermentation
After creating the inoculum at the seed
preparation stage, the inoculum is introduced into production fermentors. In
general, the fermentor is agitated, aerated, and controlled for pH,
temperature, and dissolved oxygen levels to optimize the fermentation process.
The fermentation process lasts from hours to weeks, depending on the product
and process.
Product
Recovery
When fermentation is complete, the desired
pharmaceutical byproducts need to be recovered from the fermented liquid
mixture. Solvent extraction, direct precipitation, and ion exchange may be used
to recover the product. Additionally, if the product is contained within the
microorganism used in fermentation, heating or ultrasound may be required to
break the microorganism’s cell wall. In solvent extraction, organic solvents
are employed to separate the product from the aqueous solution. The product can
then be removed from the solvent by crystallization. In direct precipitation,
products are precipitated out of solution using precipitating agents like metal
salts. In ion exchange, the product adsorbs onto an ion exchange resin and is
later recovered from the resin using solvents, acids, or bases.
Formulation
of Final Products
The final stage of pharmaceutical
manufacturing is the conversion of manufactured bulk substances into final,
usable forms. Common forms of pharmaceutical products include tablets,
capsules, liquids, creams and ointments, aerosols, patches, and injectable
dosages. Tablets account for the majority of pharmaceutical solids.
To prepare a tablet, the active ingredient is
combined with a filler (such as sugar or starch), a binder (such as corn syrup
or starch), and sometimes a lubricant (such as magnesium state or polyethylene
glycol). The filler ensures the proper concentration of the active ingredient;
the purpose of the binder is to bond tablet particles together. The lubricant
may facilitate equipment operation during tablet manufacture and can also help
to slow the disintegration of active ingredients.
Tablets are produced via the
compression of powders. Wet granulation or dry granulation processes may be
used. In wet granulation, the active ingredient is powdered and mixed with the
filler, wetted and blended with the binder in solution, mixed with lubricants,
and finally compressed into tablets. Dry granulation is used when tablet
ingredients are sensitive to moisture or drying temperatures. Coatings, if
used, are applied to tablets in a rotary drum, into which the coating solution
is poured. Once coated, the tablets are dried in the rotary drum; they may also
be sent to another drum for polishing.
Capsules are the second most common
solid oral pharmaceutical product in the United States after tablets (U.S. EPA
1997). Capsules are first constructed using a mold to form the outer shell of
the capsule, which is typically made of gelatin. Temperature controls during
the molding process control the viscosity of the gelatin, which in turn determines
the thickness of the capsule walls. The capsule’s ingredients are then poured
(hard capsules) or injected (soft capsules) into the mold.
For liquid pharmaceutical formulations, the
active ingredients are weighed and dissolved into a liquid base. The resulting
solutions are then mixed in glass-lined or stainless steel vessels and tanks.
Preservatives may be added to the solution to prevent mold and bacterial
growth.
If the liquid is to be used orally or for
injection, sterilization is required.
Ointments are made by blending
active ingredients with a petroleum derivative or wax base. The mixture is
cooled, rolled out, poured into tubes, and packaged.
Creams are semisolid emulsions of
oil-in-water or water-in-oil; each phase is heated separately and then mixed
together to form the final product.
In designing the
air-conditioning system for pharmaceutical plants, it is very important to
study the application, identify various factors affecting the particulate count
and decide the level of contamination that can be permitted.
What is Particulate?
Simply
stated, airborne particles are solids suspended in the air. The size of
contaminants and particles are usually described in microns; one micron is
one-millionth of a meter. In English units one micron equals 1/25,400 inch. To
give a perspective, a human hair is about 75-100 microns in diameter.
Air,
whether it is from outside or re-circulated, acts as a vehicle for bacterial
and gaseous contaminants brought in by the movement of people, material, etc. Since
many of these air borne contaminants are harmful to products and people, their
removal is necessary on medical, legal, social or financial grounds. There are
two main sources of particulates, external and internal sources.
External sources consist of
the following:
• Outside make-up air introduced into the
room: this is typically the largest source of external particulates
• Infiltration through doors, windows and
other penetration through the cleanroom barriers
Control Action:
•
Make-up air filtration
• Room
pressurization
•
Sealing of all penetrations into the space
Internal sources consist of
the following:
People
in the clean area: people are potentially the largest source of internally
generated particulates
- Clean room surface shedding
- Process equipment
- Material ingress
- Manufacturing processes
Control Action:
- Design airflow path to shield humans from surroundings
- Use of air showers [to continually wash occupants with clean air]
- Using hard-surfaced, non-porous materials such as polyvinyl panels, epoxy painted walls, and glass board ceilings
- Proper gowning procedures, head wear
- A super clean environment with controlled temperature and relative humidity has now become an essential requirement for a wide range of applications in Pharmaceutical Plants.
What is a
Cleanroom?
A
cleanroom is defined as a room in which the concentration of airborne particles
is controlled. The cleanrooms have a defined environmental control of
particulate and microbial contamination and are constructed, maintained, and
used in such a way as to minimize the introduction, generation, and retention
of contaminants.
Cleanroom
classifications are established by measurement of the number of particles 0.5
micron and larger that are contained in 1 ft3 of sampled air. Generally class
100 to 100,000 rooms are used in the pharmaceutical industry. [Note - rooms may
be classified as clean at class 1 or 10 for other applications, particularly in
the microchip /semiconductor industry].
Cleanrooms classified in the United States by Federal Standard
209E of September 1992 and by the European Economic Community (EEC) published
guidelines “Guide to Good Manufacturing Practice for Medical Products in
Europe, which are more stringent than U.S. FDA regulations.
U.S FEDERAL
STANDARD 209E
Table below derived from
Federal Standard 209E shows the air cleanliness classes:
Table Interpretation:
1. Class 100 (M 3.5) is
the area where the particle count must not exceed a total of 100 particles per
cubic foot (3,530 particles per m3) of a size 0.5 microns and
larger.
2. Class 10,000 (M 5.5) is
the area where the particle count must not exceed a total of 10,000 particles
per cubic foot (353,000 particles per m3 ) of a size 0.5 microns and
larger or 70 particles per cubic foot (2,470 particles per m3), of a
size 5.0 microns and larger.
3. Class 100,000 (M 6.5)
is the area where the particle count must not exceed a total of 100,000
particles per cubic foot (3,530,000 particles per m3) of a size 0.5 micron
and larger or 700 particles per cubic foot (24,700 particles per m3 ) of a
size 5.0 microns and larger.
4. All pharmaceutical
facilities belong to one or other class of cleanroom. General acceptance is:
• Tabletting facilities -
Class 100,000
• Topical & oral
liquids - Class 10,000
• Injectables class -
Class 100
EUROPEAN COMMUNITY
GUIDELINES
European Community defines cleanrooms in
alpha Grades A, B, C and D. The classification is given on two different
conditions: 1) “At-Rest” and 2) ‘In-Operation”
“At –Rest” - ‘state of cleanrooms is
the condition where the production equipment is installed and operating but
without any operating personnel.
“In- Operation” - state of cleanrooms is
the condition where the installation is functioning in the defined operating
mode with the specified number of personnel working.
Notes
Grade-A
classification is the most stringent of all. It requires air in the immediate
proximity of exposed sterilized operations to be no more than 3500 particulates
per cubic meter, in a size range of 0.5 micron and larger, when measured not
more than one foot away from the work site and upstream of the air flow, during
filling/closing operations. This applies both at “at rest” and “in-operation”
condition. Grade-A areas are expected to be completely free from particles of
size greater than or equal to 5 micron both “at rest” and “in-operation”
condition.
Besides
“at-rest” and “in-operation” cleanroom states, another condition most commonly
used by HVAC contractors is “As – Built” condition. ‘As built’ cleanrooms are
those which are ready with all services connected but without equipment and
personnel.
The HVAC contractors responsibility generally
lies up to the ‘as built’ or ‘at rest’ cleanroom stage and often the
pharmaceutical companies specify higher cleanliness levels for these stages
than the ’operational’ stage.
Typical
Examples
Typical examples of Grade- A areas include
filling zone, Stopper bowls, Open ampoules and vials making aseptic connections
Typical examples of Grade-B areas are Aseptic
preparation and filling area, Aseptic receiving area, Aseptic changing room and
solution preparation room.
These are less critical areas. Typical
examples of these areas are 1) Changing room, 2) Material Entry air locks
Comparison
of US Federal standard 209E v/s EEC
Class 100 is
equivalent to (Grades A and B)
Class 10,000
is equivalent to (Grade C)
Class 100,000 is equivalent to (Grade D)
FACILITY
CLASSIFICATION
Pharmaceutical
facility typically consists of a series of integrating classes of rooms to
match with the requirements of the manufacturing process. There are some basic
requirements that must be satisfied so that the air in the sterile rooms is
correct for the activities related to the manufacturing process. Each sterile
room must be clinically independent from the surrounding area and are produced
by “aseptic” processing. Aseptic processing is a method of producing a
sterile (absence of living organisms) product. The objective of aseptic
processing methods is to assemble previously sterilized product, containers and
closures within specially designed and controlled
environments intended to minimize the
potential of microbiological or particulate contamination.
Cleanrooms classifications differ for sterile
and non-sterile areas. These are called by many names viz.:
Non-sterilized operation = controlled area =
non-aseptic application
Sterilized operation = critical Area =
aseptic application
Controlled
Areas
U.S standards define the “controlled area” as
the areas where Non-sterilized products are prepared. This includes
areas where compounds are compounded and where components, in-process
materials, drug products and contact surfaces of equipment, containers and
closures, are exposed to the plant environment.
Requirement - Air in “controlled areas”
is generally of acceptable particulate quality if it has a per cubic foot
particle count of not more than 100,000 in size range of 0.5 micron and larger
(Class 100,000) when measured in the vicinity of the exposed articles during
periods of activity. With regard to microbial quality, an incidence of no more
than 2.5 colony forming units per cubic foot is acceptable.
In order to maintain air
quality in controlled areas… airflow sufficient to achieve at least 20 air
changes per hour and, in general, a pressure differential of at least 0.05 inch
of water gauge (with all doors closed) is recommended.
Critical Areas
U. S standards define “Critical Areas”, as
the areas where Sterilized operations are carried out. These shall have
aseptic cleanrooms.
Requirement - Air in “critical areas” is
generally of acceptable particulate quality if it has a per cubic foot particle
count of not more than 100 in size range of 0.5 micron and larger (Class 100)
when measured in the vicinity of the exposed articles during periods of activity.
With regard to microbial quality, an incidence of no more than 0.1 colony
forming units per cubic foot is acceptable.
In order to maintain air quality in sterile
areas… laminar airflow at velocity of 90 feet per minute ± 20 and, in general,
a pressure differential of at least 0.05 inch of water gauge (with all doors
closed) is recommended. No specific air change rate is specified by Fed and EEU
standards.
TYPES OF CLEANROOMS
Cleanrooms are also categorized by the way
supply air is distributed. There are generally two air supply configurations
used in cleanroom design: 1) Non-unidirectional and 2) Unidirectional.
Non-unidirectional air
flow
In this
airflow pattern, there will be considerable amount of turbulence and it can be
used in rooms where major contamination is expected from external source i.e.
the make up air. This turbulent flow enhances the mixing of low and high
particle concentrations, producing a homogenous particle concentration
acceptable to the process.
Air is typically supplied
into the space by one of two methods. The first uses supply diffusers and HEPA
filters. The HEPA filter may be integral to the supply diffuser or it may be
located upstream in the ductwork or air handler. The second method has the
supply air pre-filtered upstream of the cleanroom and introduced into the space
through HEPA filtered work stations. Non-unidirectional airflow may provide
satisfactory control for cleanliness levels of Class 1000 to Class 100,000.
Unidirectional air flow
The unidirectional air flow pattern is a single pass,
single direction air flow of parallel streams. It is also called 'laminar'
airflow since the parallel streams are maintained within 18 deg - 20 deg
deviation. The velocity of air flow is maintained at 90 feet per minute ±20 as specified
in Federal Standard 209 version B although later version E does not specify any
velocity standards.
Unidirectional cleanrooms are used where low air borne
contaminant levels are required, and where internal contaminants are the main
concern.
They
are generally of two types:
1. Vertical down-flow cleanrooms where the air flow is vertical
‘laminar’ in direction.
2. Horizontal flow where the air flow is horizontal ‘laminar’ in
direction.
In vertical down-flow arrangement, clean
make-up air is typically introduced at the ceiling and returned through a
raised floor or at the base of the side walls. Horizontal flow cleanrooms use a
similar approach, but with a supply wall on one side and a return wall on the
other.
Typically a
down-flow cleanroom consists of HEPA filtered units mounted in the ceiling. As
the class of the cleanroom gets lower, more of the ceiling consists of HEPA
units, until, at Class 100, the entire ceiling will require HEPA filtration.
The flow of air in a down-flow cleanroom bathes the room in a downward flow of
clean air. Contamination generated in the room is generally swept down and out
through the return.
The horizontal
flow cleanroom uses the same filtration airflow technique as the down-flow,
except the air flows across the room from the supply wall to the return wall.
Between the
two, the vertical down-flow pattern yield better results and is more adaptable
to pharmaceutical production.
How do Cleanrooms HVAC
different from a normal comfort air conditioned space?
A cleanroom requires a very stringent control
of temperature, relative humidity, particle counts in various rooms, air flow
pattern and pressure differential between various rooms of the clean air
system. All this requires:
1. Increased Air Supply: Whereas comfort air conditioning would require about 2-10 air
changes/hr, a typical cleanroom, say Class 10,000, would require 50 - 100 air
changes. This additional air supply helps, to dilute the contaminants to an
acceptable concentration.
2. High Efficiency Filters: The use of HEPA filters having
filtration efficiency of 99.97% down to 0.3 microns is another distinguishing
feature of cleanrooms.
3. Terminal Filtration and Air Flow pattern: Not only are
high efficiency filters used, but a laminar flow is sought.
4. Room Pressurization: With the increased fresh air
intake, cleanrooms are pressurized in gradients. This is important to keep
external particulates out of clean spaces.
SYSTEM
DESIGN
The HVAC design process begins with meetings
with process engineers, architects, and representatives from the owner or
facility user. The process and instrument diagrams (P&IDs) are reviewed,
and a general understanding of the process is conveyed to all interested
parties. Operation of the facility is reviewed, and any plans for future
additions or modifications are discussed.
After the initial meeting, a written basis of
design is produced that describes the regulations and codes that will govern
the design. Spaces are defined by function, and temperature and humidity
requirements are determined. Room classifications are listed and adjacency of
spaces and pressure relationships are documented. Any unusual or unique
facility requirements must also be designed into the HVAC system at this time,
such as emergency backup or redundancy for HVAC systems. This is also the stage
of the design process during which alternate studies are conducted to compare
options for the HVAC system. The cost of a backup or redundant HVAC supply
system may be compared with the cost of product loss or experiment interruption
should temperatures or airflow go out of control or specification. Heat
recovery from exhaust systems and thermal storage are examples of other
potential areas for study. Airflow diagrams are produced that show areas served
by a particular air handling system including supply, return, exhaust, and
transfer air between spaces. The basis of design also describes major equipment
to be used and the level of quality of components and construction material.
The efficacy of the system
design is based on proper consideration of the following factors:
1.
Building construction and layout design
2.
Defining the HVAC requirements system-wise and then room-wise. – Cleanliness
level – Room temperature, relative humidity – Room pressure – Air flow pattern
3.
Cooling load and Airflow compilation
4.
Selection of air flow pattern
5.
Pressurization of rooms
6. Air
handling system
7. Duct
system design and construction
8. Selection, location and mounting of filtration system
9. Defumigation requirement
10. Commissioning, performance qualification and validation
11. Testing and validation
12. Documentation
BUILDING DESIGN, CONSTRUCTION AND LAYOUT
Proper building design and planning of the
flow of personnel, material and equipment is essential for achieving and
maintaining the design levels of cleanliness and pressure gradients. If the
building layout and its construction are poor there is very little that an
air-conditioning system designer can do to satisfy the end-user needs.
Building Layout
From an HVAC standpoint it is desirable to
keep similarly classified areas as physically close to each other as possible
so they can be connected to the same air handling system, thereby minimizing
duct runs, cost, and air system complexity. It is also imperative that spaces
be arranged to allow people to move around without disrupting the cleanliness
or containment of the spaces.
It is NOT desirable to mix dirty and clean
systems or suites that may allow the possibility of cross-contamination from
one suite to another. Leaks can develop in a filter, or some source of
contamination could find its way through the air supply or return systems,
providing a source for cross-contamination.
Sterile zones are normally divided into three
sub zones:
1. Main sterile zone or
white zone
2. Cooling zone which is
also a white zone
3. Set of three change
rooms: black, grey and white in ascending order of cleanliness
In order to achieve a pressure gradient, it
is imperative that zones are located such that the gradient is unidirectional,
i.e. the room with the highest pressure should be located at one end and the
room with the lowest pressure should be located near the opposite end. This
type of planning can simplify balancing of system pressures to a great extent.
Entry for people to the main sterile room
should be from a set of three change rooms: black, gray and white …in that
order. Entry for equipment and material must be through “AIRLOCKS”. No area
should directly open into the sterile room.
Building
Construction
The internal particulate
generation always is the focus of any cleanroom design. The internal generation
consists of those from building elements such as walls, floor, ceiling, etc.,
from equipment, and most importantly from operators. The building construction
itself has to be "tight" with minimum of uncontrolled infiltration
and leakages. This is very important in the case of buildings for formulation
and sterile production. Materials used in the construction of the
pharmaceutical facilities should be hard-surfaced. There are few special points
of interest as noted below:
1. All material used is construction should be non chipping and
cleanable. Wall and floor finishes should not shed particulates and should
provide self-cleaning surfaces.
2. All exposed surfaces should be smooth, impervious and unbroken
3. No un-cleanable recesses and a minimum of projecting ledges,
shelves, cupboards and equipment
4. Sharp corners should be avoided between floors, walls and
ceiling
5. False ceilings and the tile joints in the floor should be
completely sealed
6. Pipes, ducts and other utilities should be installed so they do
not create recesses
7. Sinks and drains should be prohibited in grade Class 100 areas
8. All doors in the sterile area should have airtight construction.
Special gaskets should be provided on the door frame and drop seals provided at
the bottom of the door, if necessary.
9. Epoxy painting should be carried out in these areas.
Areas w/o False Ceiling
Special attention should be given to the type
of ceiling. The commonly followed trend is to eliminate false ceilings and to
provide instead a concrete slab on top of which are located the air handling
units and ducting. Cut outs in this slab are used for housing the terminal
filters. Access to these filters is from top of the slab. Care should be taken
to adequately reinforce this slab to accommodate the weight of the air handling
units, piping and ducting.
In the case of NO false ceiling is
considered, the air-conditioning system is required to be designed before slab
construction is started. Make sure:
1.
To correctly identify the location and size of the cutouts for
terminal filters. Mounting frames for terminal filters/terminal filter boxes
should be grouted at the time of casting the slab.
2. To correctly identify the location and size of the
cutouts for return air risers and inserts in the slab.
3. To correctly identify additional cutouts required for
other MEP services.
4.
To
correctly determine the air handling equipment size and location that should be
matched with the cut-out location and size.
5.
To
provide curbing at the perimeter of the cutouts to prevent water seepage into
the working area.
6.
To correctly provide floor drain locations for
air handling units.
7.
To
consider water proofing in areas where air handling units are located.
Areas with False Ceiling
1. In the case of a false
ceiling in the sterile area, the following points should be considered:
2. Inserts should be provided
for false ceiling supports and mounting of filters.
3. To prevent fungus growth
and eliminate air leakage, the false ceiling should be of NON-shedding variety,
such as aluminum or PVC coated CRCA sheet.
4. False ceiling members
should be designed to support part of the weight of terminal filters.
5. Proper sealing must be
provided between panels and between filters and panels to avoid air leakage.
Ceiling Construction
The ceiling of the
cleanroom is another potential location for contaminants to enter the clean
zone. Pressurization of the cleanroom helps to prevent this; however this can
lead to contaminants from the processes in the cleanroom being forced out into
the area surrounding the cleanroom. To reduce the chance of this happening, the
cleanroom ceiling is sealed. The type of seal is determined by the cleanliness
class of the cleanroom. For Class 1,000 and higher (less clean), the ceiling
grid can be gasketed aluminum T-bar with a 1” face tee. A Class 100 cleanroom
should have a gasketed aluminum T-bar grid with 2” face tees and Class 10 and
cleaner should have a modular / T-bar ceiling grid with a gel seal.
The gasketed T-bar system has an integral
vinyl, or similar material, gasket. The gasket is compressed between the base
of the tee and the ceiling panel or diffuser. Hold down clips is used to
maintain the compression on all non-access related panels.
The gel grid T-bar system has a groove
running the full length of both sides of the tee. The groove is filled with a
suitable sealing gel. This type of ceiling is typically used in cleanrooms
where 100% of the ceiling consists of filters or fan filter units. The filters
and/or fan filter units have a knife edge around the perimeter which goes into
the gel forming a seal.
The type of ceiling panels used in a
cleanroom ceiling also depends on the cleanliness class of the space. Class
1,000 and above (less clean) can have cleanroom approved, vinyl covered panels
or blank aluminum panels while Class 100 and cleaner can only have blank
aluminum panels.
Ceiling grid support is determined by
cleanliness class as well. Class 100 and cleaner should have all-thread rod
with strut and turnbuckles while Class 1,000 and above should have 12 ga hanger
wires to the grid and 10 ga hanger wires to the filters. The hanger wires
should be installed at the grid intersections.
Summarizing
HVAC REQUIRMENTS
Define the HVAC requirements system-wise and
then room-wise. The requirements defined are:
1) Room temperature
2) Relative humidity
3) Cleanliness
level and
4) Room pressure
Room Temperature (T)
Room temperature (T) is not critical as long
as it provides comfortable conditions. Generally areas are designed to provide
room temperatures from 67 and 77°F with a control point of 72°F. Lower space
temperatures may be required where people are very heavily gowned and would be
uncomfortable at “normal” room conditions.
Relative Humidity (RH)
Relative humidity (RH) on the other hand, is
of greater importance in all the production areas. While most of the areas
could have a RH of 50 ± 5%, facilities designed for handling hygroscopic
powders need to be at 30 ± 5%. Automatic control of the RH is essential for
maintaining continued product quality. Control of humidity is necessary for
personal comfort, to prevent corrosion, to control microbial growth, and to
reduce the possibility of static electricity. We will discuss more about the RH
control in the subsequent sections.
Control Airborne Particles
(C)
Of all the design goals,
it is the quality of air cleanliness of the space and prevention of
contamination which are of utmost importance. Externally generated particulates
are prevented from entering the clean space through the use of proper air
filtration. The normally accepted air quality standards for both sterilized and
non-sterilized areas are tabulated below:
Room Pressure
Differential (DP)
Cleanroom positive pressurization is desired to prevent
infiltration of air from adjacent areas. The normally accepted air
pressurization standards for both sterilized and non-sterilized areas are
tabulated below:
COOLING LOADS
Pharmaceutical buildings as a rule are
totally enclosed without any fenestrations. This is to maintain a 'tight'
building to minimize uncontrolled infiltration. As a result, the room sensible
loads are essentially a contribution from process equipment, lighting and
personnel. Fan heat from recirculating fans can also be a large heat
contributor in clean spaces. The density of equipment loads is low excepting in
the tablet manufacturing facility covering granulation, drying and tabletting.
Heat-loss calculations
must also be made to determine heat loss through walls, roof, and floor. No
credit should be taken for process heat gain in this calculation, since the
process could be dormant and the space would still need to be maintained at
proper temperature.
A major contribution of the cooling load
comes from outside air entering the air handling unit. There is also
considerable diversity in the equipment loads based on the production patterns.
All these result in a low room sensible load density varying from as low as 15
Btu/hr sq-ft to 40 Btu/hr sq-ft. Hence the system design lays emphasis on
control and maintenance of relative humidity. The room temperature is normally
held at 70°F, whereas the relative humidity is held at 50± 5% in most of the
areas. In a few areas it is maintained at 35± 5% or lower depending on the
product characteristics.
Formulas to determine
cooling loads are available from HVAC handbooks and ASHRAE standards.
AIRFLOW
SHEETS
Once the cooling load is determined, the next
step is to calculate the dehumidified airflow using psychrometric analysis or
computer analysis. These results are compared with airflow quantities required
to establish the minimum air required to satisfy both the space cooling load
requirements and air cleanliness classification.
The airflow sheets should
be developed on full-size drawings and should show air quantities supplied,
returned, and exhausted from each space. They also must show air transferred
into and out of spaces, and, while quantities should be shown, they will
probably require field modification to attain pressurization. The airflow sheet
is a useful tool for transfer of information to the owner or user, for agency
reviews, for transmission of information to
HVAC designers, and for other engineering disciplines. These documents are also
invaluable to construction contractors and for system checking by construction
managers and balancing contractors. Airflow sheets provide a pictorial
description of each air system and show how the elements comprising the system
are related.
AIRFLOW PATTERN
The air distribution has to be appropriate with the class
of cleanroom. Air turbulence in the space can cause particulates which have
settled onto the floor and work surfaces to become re-entrained in the air. Air
turbulence is greatly influenced by the configuration of air supply and return
grilles, people traffic and process equipment layout.
The following measures are normally taken to control the
air flow pattern and hence the pressure gradient of the sterile area:
1. Class 100 and lower zones must necessarily have
unidirectional (laminar) flow with 100% HEPA filter coverage in the ceiling or
wall. Return must be picked up from the opposite side.
2. Air flow velocities of 90 fpm ±20 (70
fpm to 110 fpm) are recommended as standard design for Class 100 cleanroom
systems.
3. The vertical down-flow configuration is preferred. Per EEC
standards, laminar work station with vertical flow requires 0.3 m/s velocity
whereas the horizontal work stations require 0.45 m/s velocity. When horizontal
flow is used the work place must be immediately in front of the clean air
source so that there is nothing in between which could emit or cause
uncontrolled turbulence and consequent contamination.
4. Class 1000 and above are generally non-unidirectional with the
supply air outlets at the ceiling level and the return air at the floor level.
5. This air should be supplied at a much higher volume than its
surrounding area ensuring a higher velocity and pressure in the clean zone
relative to the perimeter.
Return
Air System
The air return system is another critical
component of the cleanroom air distribution system. The return points shall be
positioned low down near the floor in the walls and spaced as symmetrically as
building construction allows. Return grilles shall be made as long as
convenient to increase the collection of dust particles over a larger area.
Return air grilles in the main sterile zones
should be located to avoid dead air pockets. While locating the return grille,
care should be taken to avoid placing the grille near a door opening into an
adjoining lower pressure room. This is done to prevent creation of a low
pressure zone near the door, thus preventing air leakage from the low pressure
to high pressure room at the time of door opening.
On each return air riser
manually operated dampers shall be provided for control. These dampers should
preferably be operated from the non-sterile areas.
Mixed Areas
It is possible to create Class 100 space
within Class 10,000 areas at background. For example, if a small localized
operation in big Class 10,000 volume requires Class 100 standard, there is no
point to put the entire area as Class 100. This will be very expensive. For
such areas, install “localized laminar flow workstations”, which are commercially
available in horizontal or vertical flow patterns generally recirculating
within the clean space.
AIR CHANGES
Air change rate is a measure of how quickly
the air in an interior space is replaced by outside (or conditioned) air. For
example, if the amount of air that enters and exits in one hour equals the
total volume of the cleanroom, the space is said to undergo one air change per
hour. Air flow rate is measured in appropriate units such as cubic feet per
minute (CFM) and is given by
Air flow rate = Air changes x Volume of
space/ 60
The normally accepted air
change rates for both sterilized and non-sterilized areas are tabulated below:
Even though various design guidelines and
standards are available, there is no clear-cut guidance for air changes per
hour especially for “sterilized areas”.
Table below indicates a
typical range of air change rates generally used to achieve the desired room
cleanliness classifications and to meet federal and local regulations. These
air change rates vary widely in actual practice due to the level of activity,
number and type of particulate generators in a room (such as people and
equipment), and room size and quality of air distribution. It is generally best
to use historic data to establish airflows, which is usually done with
significant input from the owner based on past experience or preference. There
is nothing sacred about an air change rate as long as minimum airflow rates
required by code are maintained. The goal is to achieve desired particulate
cleanliness levels and stay at or above a 20 air changes/h minimum.
How to
estimate air change rate?
Most pharmaceutical cleanrooms depend on the
principle of dilution to control their particles. The air-change rate leads to
dilution of space. Simply put, the dilution rate in terms of air change rate
per hour is given by following equation, assuming no infiltration as the room
is pressurized:
v
= g / (x – s)
Where
• s is the supply air particulate concentration in
particles per ft
• v is the supply air volume flow rate in terms of
air-change rate per hour
• g is the internal generation rate in particles per ft3 per
hour
• x is room or return air concentration in particles per ft3
Example
For a typical Class 10,000
cleanroom space with a typical internal generation of approximately 5,000 per
CFM, and supply air through 99.97% HEPA filters, what shall be the required
air-change rate?
Solution
The
supply rate can be estimated using equation:
v
= g / (x – s)
Where
g = 5000 * 60 ft3 per hour
x = 10,000
s = 3 for 99.97% efficient HEPA filters
v
= 5000 * 60 / (10000 – 3) = 30 air changes per hour
Of course, in the case
that internal generation is significantly higher, more air changes would be
required.
It is important to note
that high air change rate (ACR) equate to higher airflows and more energy use.
In most cleanrooms, human occupants are the primary source of contamination.
Once a cleanroom is vacated, lower air changes per hour to maintain cleanliness
are possible allowing for setback of the air handling systems. Variable speed
drives (VSD) should be used on all recirculation air systems allowing for air
flow adjustments to optimize airflow or account for filter loading. Where VSD
are not already present, they can be added and provide excellent payback if
coupled with modest turndowns. The benefits of optimized airflow rates are:
1) Reduced Capital Costs -
Lower air change rates result in smaller fans, which reduce both the initial
investment and construction cost. A 20 percent decrease in ACR will enable
close to a 50 percent reduction in fan size.
2) Reduced Energy
Consumption - The energy savings opportunities are comparable to the potential
fan size reductions. According to the fan affinity laws, the fan power is
proportional to the cube of air changes rates or airflow. A reduction in the
air change rate by 30% results in a power reduction of approximately 66%. A 50
percent reduction in flow will result in a reduction of power by approximately
a factor of eight or 87.5 percent.
Designing a flexible
system with variable air flow can achieve the objectives of optimized airflow
rates. Existing systems should be adjusted to run at the lower end of the
recommend ACR range through careful monitoring of impact on the cleanroom
processes.
PRESSURIZATION
Pressurization prevents the infiltration from adjacent spaces.
Pressurization of clean areas is required to keep products from being
contaminated by particulate and/or to protect people from contact with harmful
substances by physical means or inhalation. This can be easily accomplished by
supplying more air than the cumulative of what is returned, exhausted or leaked
from the room.
Standard 209E specifies
that the minimum positive pressure between the cleanroom and any adjacent area
with lower cleanliness requirements should be 0.05 in. w.g with all entryways
closed. During facility operation as doors are opened, the design differential
is greatly reduced, but air must continue to flow from the higher to lower
pressure space, even though at a reduced flow rate. To maintain a differential
of 0.05 in water, a velocity of approximately 900 ft/min (4.7 m/s) should be
maintained through all openings or leaks in the room, such as cracks around
door openings. In theory the actual required velocity is less, but in actual
practice it is prudent to use 900 ft/min. [Note that one-inch water gauge
pressure is approximately equivalent to wind velocity of 4000 feet per minute].
The amount of
air being returned has a bearing on room pressurization and will depend on the
process taking place within the clean space. For a space requiring positive
pressurization, the return air volume is typically 15% less than the total
supply air volume. While calculating supply air quantities for various rooms,
allowances should be made for process equipments like tunnels that cross room
pressure boundaries and open doors, if any. Of particular importance is exhaust
air from equipment and hoods that may be on or off at different times during
occupied periods. These variations must be dynamically compensated for to
maintain room pressurization. To maintain the required balance, numerous
systems are employed using manual and automatic dampers, constant and variable
volume air control boxes, and elaborate airflow sensing devices. These components
are combined with control systems and sensing devices to ensure that the room
pressurization is maintained.
The
pressure gradients are monitored with 'U' tube manometers or magnahelic gauges.
Alarm and warning systems may also be provided when the pressure gradients are
disturbed.
Pressure
Gradient
There should be a net
airflow from aseptic rooms to the non-aseptic areas. This is possible only if
there is pressure gradient between two adjacent rooms. Air always flow from
high pressure to low pressure region. Pressure between two rooms is
differential pressure “DP”.
With reasonably good building construction and airtight
doors and windows, it is normally possible to achieve and maintain the
following pressures between various zones.
Note:
[10 Pa = 1 mm
w.g. = 0.04 inch w.g.]
Where major demarcations of pressure are
required, air locks are used. These are small rooms with controlled airflows
acting as barriers between spaces. It minimizes the volume of contaminated air
that is introduced into the cleaner room when its door is opened…remember, with
ZERO pressure differential and on open door, the entire volume of the dirtier
room can eventually find its way to the cleaner room. It is important that
• Doors open/close FAST (to minimize time of contamination). Both
airlock doors should not be opened simultaneously.
• High air changes (high airflow or small volume room) to permit
faster “recovery”.
• People use smaller airlock (faster recovery time = less time to
wait in airlock)
The pressure differential exerts a force on
the door. If the force is too great (0.15 in water/36 Pa), the door may not
close fully or may be difficult to open. This is particularly important in
large complex facilities where many levels of pressurization may be required.
Many facilities now use sliding doors, and it is essential that the seals be
carefully designed to allow minimum leakage and proper containment or
pressurization.
Alarms that sound to indicate loss of
pressurization are valuable features and essential in the HVAC design of
critical areas.
Room Seals
and Doors
In most facilities the openings around the
doors between rooms are where leaks occur due to pressure differentials between
rooms. In making rooms tight any room openings must be sealed with a proper
sealant that will not promote growth of organisms and can be easily cleaned.
Areas to be sealed include ceiling tiles, lighting fixtures, pipe penetrations,
telephone outlet penetrations, and any cracks or openings that appear in the
structure. A typical door would have the following dimensions and crack area at
the perimeter: door size, 3 ft wide by 7 ft high; cracks at top and sides, 1/8
in with an undercut of 1/4 in. The calculated area around the door is equal to
0.24 ft2.
To achieve 0.05 in water pressure differential across the door, approximately
215 CFM of airflow through the cracks is required. Door seals around the top
and sides are usually made of closed cell neoprene and should generally be used
to reduce the crack area. To reduce the undercut, a drop type seal, which is
commercially available, should be used. The drop type is preferred to a wipe
type, since it will not mar or leave residue on the floor. Air used for
pressurization must be accounted for in system calculations. Air through cracks
or openings is accounted for as transfer air and shown in the HVAC room balance
table.
FILTRATION
Proper air filtration is crucial for
cleanroom controls. In dusty production areas such as grinding, granulation,
coating, tabletting etc., the filters not only control the atmosphere
contamination but also hold the internally generated particulates.
Atmospheric dust is a mixture of dry
particles, fibers, mist, smoke, fumes, live or dead organisms. The air-borne
particle size varies from 0.01 micron to as much as 100 microns. Less than 2.5 micron particles are considered as
fine and particles over 2.5 micron is regarded as “coarse”. Fine particles are
airborne for a longer time and could settle on vertical surfaces. Coarse
particles, products of mechanical abrasion like in grinding and granulation
departments, have lower airborne life time and are subject to gravitational
settlement. The air conditioning systems in the pharmaceutical industry have to
handle both fine and coarse particulates depending on the production pattern
and the filter regime has to be appropriate.
Air Filters
• Air filters capture solid materials
• Can be “roughing” filter to capture a significant percentage of
total mass (30%)
• Can be “high efficiency” to capture a higher percentage of mass,
plus some of the “weightless” fine particles (85% - 95%)
• Can be “high efficiency particulate” to remove virtually 100% of
the material weight and 99.97% or more of all particles
Terminal HEPA Filters
HEPA (High efficiency particulate air) filters have 99.97%
to 99.997% removal efficiency on 0.3μ particles. In other words, only less than
0.03% of all particles of 0.3 microns or larger can get through such a filter.
So if the return air contains 10,000 particles per ft3, its
concentration would be reduced down to three particles per ft3 after
it goes through the filter. Ultra low particulate air (ULPA) filters have
99.9997% removal efficiency on 0.12μ particles, but these are generally
recommended for cleanliness lever of Class 10 and low (more cleaner
classification), primarily for semi-conductor industry.
HEPA filters use sub-micron glass fiber media housed in an
aluminum framework and are available in two types of constructions: 1) Box type
and 2) Flanged type.
Box type filters are more suitable for housing within the
ceiling slab cutout where removal of filter is from above. Whenever filter
removal is not from above e.g. in case of filter being mounted in false
ceiling, flanged type of filters is required. With flanged type of
filters, additional housing is also required to facilitate the mounting of
filters and transfer
the load to false ceiling members. Aluminum / stainless steel slotted type
protective grilles can be provided under the terminal filters. The housing and
grilles should be epoxy/stove enamel painted. Sealing of filters to frames is
an installation problem and is best solved by using a filter frame with a
gel-like seal into which the filter fits. The sealant selected should not
promote growth of organisms and can be easily cleaned.
These filters are available in thicknesses of
6” and 12” and have pressure drop of 1 inch-w.g. when clean and generally need
to be replaced when the pressure drop exceeds 2 inch-w.g. The most popular HEPA
filter location is in the room ceiling using standard laminar flow outlets
nominally 24” x 48”.
Pre-filters to HEPA Filters
In order to prolong the service life of HEPA filters,
pre-filters are recommended to filter out majority of particles above 1 micron.
However, dust holding capacity of these filters is poor. Therefore, in case the
application requires a filtration system with good dust holding capacity, bag
type filters with fiberglass scrim cloth media are recommended to give
efficiencies ranging from 85% (down to 20 microns) to 99.97% (down to 5
microns).
Pre-filters are available in various sizes with 6” and 12”
thickness and with pressure drop in the range of 0.2 to 0.25 inch- w.g.
Pre-filters are normally mounted in a separate plenum with access door after
supply air fan discharge at an appropriate location. Normally flanged filters
are used for mounting in such plenums. It should be convenient to clean and
replace these filters without disturbing the rest of the filtration system.
Roughing Filter
These filters are normally provided before the cooling coil
in the air handling unit and at fresh air intakes. Efficiency of these filters
is in the range of 80% down to 20 microns and they can be easily cleaned by
washing. Filters with synthetic media sandwiched between HDPE layers in
thickness of 2 inches are highly suitable for such applications.
Filters Performance Ratings
Filters are distinguished by their efficiency, airflow
resistance and dust holding capacity. Air filters are commonly described and
rated on their collection efficiency, pressure drop (or airflow resistance),
and particulate-holding capacity. The American Society of Heating,
Refrigerating, and Air Conditioning Engineers (ASHRAE) have developed standards
52.1-1992 and 52.2-1999 that classify filters in terms of “Arrestance” and
“Efficiency”.
Per
ASHRAE standards 52.1-1992, Arrestance means a filter’s ability to capture dust
and describes how well an air filter removes larger particles such as dirt,
lint, hair, and dust. The dust holding capacity of a filter is
the amount by weight of standard dust that the filter will hold without
exceeding the resistance 0.18 inch-w.g. for low-resistance filters, 0.50
inch-w.g. for medium-resistance filters and 1.0 inch-w.g. for high-resistance
filters. Be aware that arrestance values may be high; even for low-efficiency
filters, and do not adequately indicate the effectiveness of certain filters
for chemical or biological protection. Dust spot efficiency measures
a filter's ability to remove large particles; those tend to soil building
interiors. Dust arrestance can be expressed as μa = 1 - Ca / Cb
Where
μa = dust
arrestance
Ca = dust
concentration after filter
Cb = dust
concentration before filter
Since large
particles make up most of the weight in an air sample, a filter could remove a
fairly high percentage of those particles while having no effect on the
numerous small particles in the sample. Thus, filters with an arrestance of 90
percent have little application in cleanrooms.
Per ASHRAE standards
52.2-1999, Efficiency measures the ability of the filter to
remove the fine particles from an airstream by measuring the concentration of
the material upstream and downstream of the device. If a supplier of filter
only indicates efficiency as 95% or 99%, it does not really mean anything
unless it specifies the particle size range.
The ASHRAE Standard 52.2-1999 quantifies filtration
efficiency in different particle size ranges and rates results as MERV (Minimum
Efficiency Reporting Value) between 1 and 16. This numbering system makes it
easier to evaluate and compare mechanical air filters and eliminates some of
the confusion regarding the overall effectiveness of any type of a mechanical
air filter on removing airborne particulates, especially those that are less
than 2 microns in size. A higher MERV indicates a more efficient filter.
Filter Testing
The efficiency of a filter is of paramount
importance and must be measured in an appropriate way. The common tests on the
filters include the dust spot test and DOP tests. The dust spot test is a
measure of the ability of the filter to reduce soiling and discoloration. High
efficiency filters are tested using Di-octyl Phthalate (DOP) method.
The DOP test is conducted by counting
upstream and downstream particulates through a light scattering photometer or
any other particulate counter. Test particulates are of uniform 0.3 micron
diameter with a density of 80mg/cum produced by condensation of DOP vapor
(Dioctyl phthalate or bis - 2 ethylexyl). In essence, if ten thousand (10,000)
0.3 micron sized particles are blown into a HEPA air filter, only 3 particles
are allowed to pass through. Thus, you get the 99.97% at .3 micron rating.
Typically the filters are
shop tested and the manufacturers typically provide the quality certification
for required efficiency to the end user. Table below is a guide line to filter
selection.
All filters are dry type with synthetic and glass fiber.
While pre-filters could be cleanable, the final filters are disposable.
BASIC HVAC SYSTEMS
1. Once –thru Air – Air is conditioned, enters the space
and is discarded
2. Recirculated Air - Air is conditioned, enters the space
and portion is reconditioned. Some may be discarded.
Once – Thru HVAC
What are
the advantages of this system?
1. Fresh air – lots of it
2. Can handle hazardous materials, although will need to clean up
air leaving the space
3. Exhaust duct is usually easy to route as high velocity =
smaller diameter
Disadvantages
1. Expensive to operate, especially when cooling and heating
2. Filter loading very high = frequent replacement
3. Potential need for dust collection/scrubbers/cleanouts
Applications
1. Labs with hoods, potential hazards
2. Bulk Pharmaceutical Chemical (API) plants handling flammable
materials
3. Oral Solid Dosage (OSD) plants where potent products/materials
exposed
4. Where high potential of product cross-contamination –
segregation
5. Some bio API facilities with exposed potent materials
Recirculated
HVAC
In
pharmaceutical facilities large quantities of air may be required to promote
unidirectional flow and air cleanliness. This is particularly true in a class
100 space. In many cases the large quantities of air exceed the requirements
for cooling, so it is desirable and possible to recirculate air within the
space and only pass enough air through the air handling unit to perform the
heating or cooling.
What are
advantages here?
1. Usually less air filter loading = lower filter maintenance and
energy cost
2. Opportunity for better air filtration
3. Less challenge to HVAC = better control of parameters (T, RH,
etc)
4. Less throw-away air = lower cooling/heating cost
Disadvantages
1. Return air ductwork routing to air handler may complicate above
ceiling
2. Chance of cross contamination = requires adequate supply air
filtration (an sometimes return air filtration)
Applications
1. Classified spaces such as sterile manufacture (few airborne
materials, very clean return air)
2. Finished oral solid dosage (OSD) manufacture where product is
not airborne with other products in the facility
3. Final bulk APIs, usually with dedicated
air handler for each room
Constant
Volume Systems
The most
reliable system for pharmaceutical manufacturing areas is constant volume
system with terminal reheat (CVRH). This is because; ensuring constant pressure
gradient between the adjacent areas is of prime importance.
In a terminal reheat
system the air leaving the cooling coil is set at a fixed temperature, and the
terminal reheat responds to a space thermostat, turning on heat to satisfy the
load. This can waste energy, since air is cooled and then reheated. Many energy
codes prohibit this practice for comfort applications, however, where close
control of temperature and humidity is required for process areas the energy
conservation requirement is waived. The advantages of reheat systems are that
humidity is always controlled (since dehumidification always takes place at the
cooling coil) and each space or zone that
needs temperature control can easily be accommodated by adding a reheat coil
and thermostat. Another advantage of the CVRH system is that airflow is
constant, which makes balancing and pressurization easier to main maintain. A
reheat system is probably the simplest and easiest of all systems to understand
and maintain.
Variable
Air Volume Systems
A variable air volume (VAV) system is
generally used in administrative areas and some storage spaces where pressure
control is not critical, humidity control is not essential, and some variations
in space temperature can be tolerated. The VAV system works by delivering a
constant temperature air supply to spaces with reductions in airflow as cooling
loads diminish. This eliminates the energy used for reheat and saves fan
energy, because the total amount of air moved is reduced.
Some form of perimeter
heating must be supplied for spaces with exterior walls or large roof heat
losses. The perimeter heating can be baseboard radiation or some form of air
heating using heating coils. Finned radiation or convection heating devices
should not be used in clean spaces, since they
are not easily cleaned and allow places for unwanted particulate buildup.
Combinations of systems can be used, especially if variable quantities of
supply and exhaust air are required for fume hoods or intermittent exhausts.
HVAC EQUIPMENT SPECIFICATIONS
Air Handling Unit
Pharmaceutical air handling systems support
clean aseptic environments, so the equipment must be air-tight and epoxy
coated.
Conventional air handling units consist of
filters, coils, and fans in a metal casing, with an insulation liner applied to
the inside of the casing. For pharmaceutical applications the unit casing must
be a double skin sandwich of metal with insulation between the metal sheets to
provide a smooth, cleanable interior surface that does not foster the growth of
organisms.
Units should contain good
access doors, view ports, electrical convenience outlets, and interior lighting
for maintenance. The casings should be tightly sealed and designed for
pressures that are higher than commercial applications due to the generally
high system air pressures required for pharmaceutical applications. All
sealants and lubricants exposed to the airstream should be food grade to
minimize the chance of air contamination.
Chilled water or propylene glycol solutions
are generally used for cooling and dehumidification. Direct expansion
refrigerant, in which the refrigerant is in the air unit coil, may be used, but
these systems are less reliable than chilled water or glycol and are more
difficult to control in the narrow air temperature ranges required.
Units designated as
draw-through have the coils on the suction side of the fan. Blow-through units
have the coils on the discharge side of the fan and have the advantage of a
filter downstream of the coils, reducing potential contamination of the supply
duct system. On blow through units an air distribution plate must be installed
to properly distribute air evenly over the filter and coils.
While selecting the fan, it should be ensured
that at the lower speed the fan does not operate in the un-balanced region.
Fans should be provided with a shaft seal near the bearings.
Cooling coil section should be provided with
sandwich type of drain pan to collect condensate. It may also be necessary to
provide an eliminator after the cooling coil in order to prevent water carry-over
into the system.
In case of a heating coil, at least a 0.5
meter space should be kept between coils. All sections consisting of
pre-filters, cooling coil, heating coil, etc should be mounted in between the
SA and RA fans.
Two sets of fresh air dampers
should be provided, one for 10% to 20% and the second for 100% of fan capacity.
These dampers are located on the suction side of the return air fan. Proper
access should be provided in each section of the air handling unit for routine
maintenance and cleaning. 100% intake damper is especially useful during
“defumigation” operation discussed later in the course.
Air
Handling Unit Location
To avoid cross contamination independent air
handling systems should be provided for various discrete operations like
manufacturing, coating, tabletting, inspection and packing. In some departments
there is further segregation of operations which requires a certain degree of
control, if not an altogether independent air handling unit.
Air handling systems should be located on a
separate equipment floor or zone in order to facilitate service and maintenance
without disturbance to the sterile room. They should also be located as close
as possible to the main rooms they are serving to minimize larger and longer
duct runs.
Location of outdoor
air-inlet louvers must be carefully considered. Intakes should be located on
the building sidewall high off the ground to minimize dust intake. Intakes
should also be away from truck docks or parking lots, where undesirable fumes
and particulate are generated. In locating inlets the prevailing winds should
also be considered, and any nearby exhausts or fume concentrations should be
avoided to prevent recirculation of exhaust air back into the supply system.
Exhaust
Fans Location
Building exhausts are generally collected and
ducted to exhaust fans in groups or clusters. Exhaust fans should be located as
near to the building discharge as possible since this keeps the duct under a
negative pressure and any leaks will be into the duct, and not contaminated air
from the duct into an occupied space or mechanical room. For this reason roof
locations of fans are preferred, even though this may make service difficult in
severe weather conditions. When fans are located in mechanical rooms or interstitial
spaces, it is essential to tightly seal the discharge duct before it exits the
building in a roof vent or wall louver. Roof penetrations should be kept to a
minimum to prevent leaks. Fumes and toxic exhausts should be extended through
the roof and terminated well above the roof line in a suitable stack head.
Extremely toxic or
dangerous active biological agents may require HEPA filtration or other
treatment, such as incineration, before exhaust to the atmosphere.
Return Fans
Return fans are recommended on systems with
long duct returns where pressure drops greater than 0.5 in water (120 Pa) are
expected. This allows proper total system balance and minimizes suction
pressure required from the supply fan. If a return fan is not used, the
capacity of the supply fan can be overextended and it may be difficult to limit
and properly control the amount of outside air being admitted to the unit.
Outside air fluctuations are also more susceptible to exterior wind conditions.
Return fans are also
needed when required to provide a negative pressure in rooms that require
containment. Return fans can be of standard centrifugal type or an in-line
type, which works nicely for installation directly into return ducts in crowded
equipment rooms. Return fans may also be required to handle varying quantities
of air or provide a constant flow of air at varying pressure conditions. To
achieve these conditions some form of damper control, inlet vane, or variable
frequency drive motor control is generally used.
Redundancy
If return or exhaust fans
are used as part of maintaining containment, it may be desirable to have a
backup fan or redundant system. This is essential, if loss of containment can be harmful to humans or would result in an expensive loss
of product. Airflow switches, which give a warning in case of fan system
failures, are also desirable options for critical systems. The airflow sensing
method to prove flow is preferred to an electrical motor indication since the
motor could be running with a broken fan belt and the operator would not know
that the fan is not moving air.
Dehumidifiers
Dehumidifiers are used to
control relative humidity (RH) to lower levels. RH of 50±5% can be achieved by
cooling the air to the appropriate dewpoint temperature. When chilled water is
supplied at 42–44°F to the cooling coils, a minimum dew point of about 50–52°F
can be obtained. This results in a minimum room relative humidity of
approximately 50% at 70°. Spaces with high moisture content, it is important to
use a cooling coil that is deeper i.e. with higher number of rows. Sometimes
additional brine cooling coil is incorporated to further dehumidify the supply
air. This will lead to lowering of supply air temperatures downstream the
cooling coil, which is reheated by hot water coil or electrical strip heaters
before dumped into the space.
In some cases where hygroscopic (products sensitive to
moisture) materials are handled, the room RH requirement may be as low as 30 to
35% and may require the use of chemical dehumidifiers. Chemical dehumidifiers
are commercially available air handling units that contain a sorbent material
(desiccant) that can be a solid or liquid. Wet dehumidifiers use absorbents
that change physically during the process. Lithium salt solutions are generally
used to remove moisture from conditioned air and are then regenerated by heat,
usually using a steam heat exchanger. Dry dehumidifiers use adsorbents that do
not experience phase changes during the process. Silica gel and activated
alumna are generally used. A rotating wheel is commonly used to remove moisture
from the conditioned air. The wheel is regenerated by passing heated outdoor
air over the wheel to dry it out. Steam or electric coils are usually employed
for regeneration. Depending on the amount of dehumidification required and the
amount of outdoor air (usually with a high moisture content), it may be best to
combine the dehumidifier with a conventional air handling unit and only
dehumidify a small portion of the air or just the outdoor air. The dehumidifier
has a high initial cost compared with a conventional air handling unit. The
size should be optimized to do only the required duty with an appropriate
safety factor. Knowledgeable vendors in this specialized area should be
consulted to find the best combination of dehumidification equipment, system
arrangement, and control for the application. These systems also require
considerable physical space, energy consumption, and service—important criteria
to be considered in system selection.
Humidifiers
In drier locations, makeup
air may require the addition of moisture for RH control. There are many
commercially available humidifiers, but the most commonly used is “steam grid”
humidifier. These are controlled by modulation of a steam valve at the humidifier,
and include a chamber to prevent condensation and water droplets in the duct.
The valve is controlled by a signal located in the return or exhaust airstream
or in a room humidistat. A high-limit stat is placed in the duct downstream of
the humidifier to override the controlling stat and prevent condensation in the
duct. Placement of the humidifier in the duct is critical and must follow the
manufacturer’s recommendations to prevent condensation and provide proper
dispersion space. It is important to use clean steam, not plant steam, which
may contain boiler chemicals and impurities from deteriorating piping and
equipment.
Ductwork
Design, Materials & Cleanability
Duct
Pressures
Ductwork in pharmaceutical
facilities tends to have higher system pressure due to extensive use of
filters, volume control devices, and physically complex arrangements. The duct
system pressures must be calculated and clearly stated on the contract
documents to allow the fabricator to provide the proper metal thickness and construction
methods for the required system pressures. System pressures will also change as
the system is operated with filters that get dirty or space pressure conditions
that vary. Duct systems must allow for these pressure fluctuations and the fans
may require speed controls, inlet vanes, or variable pitch blades to match the
varying flow and pressure conditions.
Duct materials and shape
Unlined
galvanized steel, stainless steel or aluminum ductwork is used in rectangular,
round, and elliptical (or flat oval) configurations for the majority of the
systems. Round ducting is a natural choice, being self cleaning in shape,
wherever space permits.
Because galvanized duct
can flake off or rust, it should not be used downstream of the HEPA filters to
avoid contamination from the duct system itself. When the HEPA filter is
located upstream of the room terminal and a long run of duct is present, the
material of choice for the duct is stainless steel, but this is expensive and
its use should be minimized. Many systems may also be fumigated or cleaned in
place, and the duct material chosen should not be affected by the cleaning
agent.
Cleanability
Cleanability of duct
systems is important to ensure that if an installed system gets dirty or
contaminated it can be cleaned. In the design stage care must be taken to
locate access doors in the duct, where they can be easily reached without
compromising a process or violating a controlled space. All sealed duct shipped
to the site should have only end seals broken, and then quickly resealed,
during final installation. In very critical applications the duct is factory
cleaned and sealed before shipment to the site. This step removes the oil and
other contaminant present during duct construction but is expensive. It may be
difficult to find sheet-metal fabricators willing to do this work, since they
are not always set up for such procedures.
Following
precautions should be taken:
1. Ducts should be sealed with silicone sealant at longitudinal
joints in order to make the system airtight. Rubber gaskets should be used at
transverse joints.
2. GI flanged joints must be avoided and instead pocket slips or
angle iron flanged joints should be used.
3. No acoustic insulation should be provided inside the ducts.
4. Dampers provided in the system should be of compatible duct
materials and should have extended handle to accommodate insulation thickness.
5. Return air risers should be designed for velocities not
exceeding 1800 fpm with a minimum velocity of 1200 fpm at the highest point in
order to carry particulate matter along with return air. However, the inlet
velocity at the return grille should be in the range of 300 to 400 fpm
gradually increasing the same to 1200 to 1800 fpm.
6. Grilles and diffusers should be flush mounted into ceiling,
walls or duct work and all such grilles shall be fabricated from stainless
steel or stove enamel/epoxy coated construction.
7. Whenever terminal filters are mounted in the false ceiling,
proper sealed access door should be provided to reach the dampers above each
filter.
Supply
Terminals
In clean spaces, the
desired distribution of air is unidirectional. This carries particulate from
the ceiling to the floor return and helps to prevent airborne particulate
matter from recirculating and contaminating the work space. In most cases it is
desirable to recirculate air within a space through a filter since the return
air has less particulate than typical outdoor air and does not require
extensive heating and cooling. Air terminals should be selected of materials
that are non-flaking, non-oxidizing, and are easily wiped clean.
Return
Terminals
Return terminals are also an important
consideration and are generally located low in the walls for cleanrooms. In
class 10,000 to 100,000 rooms low cleanable wall registers are generally used.
In cleaner areas low return wall systems, termed air walls, are used.
The air wall is an almost continuous opening at the base of the wall with the
air ducted up in the wall system and collected for return to the air handling
system. Air wall inlets are generally located not more than 15 ft in plain view
from a supply terminal to reduce the likelihood of turbulence.
The material of
construction for the return grilles will be determined by the process taking
place in the clean space, though stainless steel is used quite often for its
appearance and cleanability. Due to its corrosion resistance, the use of
stainless steel grilles also allows for processes to be changed periodically
without changing grilles.
Defumigation
Sterile areas are periodically fumigated with
formaldehyde vapor that is circulated through areas and air-conditioning
equipment in order to sterilize the system. However, formaldehyde vapor must be
removed effectively after fumigation is over before starting the actual
operations. During defumigation 100% fresh air is provided and this is fully
exhausted to remove formaldehyde vapor. The fresh air and exhaust air ducting
should be designed for 100% air volume with appropriate dampers to re-set at
normal position during normal operation sequence.
The procedures must be
developed to accommodate a product spill or accident in a contained space. The
ramifications of a spill on the air system, controlled space, and adjacent
operations must be evaluated. Cleanup procedures could include fumigation of
the air system, which would require operation of a relief connection to the
ductwork for venting the fumigant.
EMERGENCY
ELECTRICAL POWER
An essential step in the HVAC design process
is coordination with the electrical design team. Motor lists for HVAC equipment
must be prepared and reviewed with the electrical design team. The need for
motors designated for emergency power, variable speed, reduced voltage
starting, or other special characteristics must be communicated to the
electrical designers early in the design process. The sizing of the emergency
generator can be greatly affected by motors required on emergency power from
the HVAC system. Fans, equipment, or sensing devices that require interlocks
must also be picked up by the electrical designers. The motor list must be kept
up to date from project inception through commissioning. The motor list is
useful for a reviewing agency, a valuable tool in training plant operators, and
a great aid in understanding the HVAC system.
BUILDING CONTROL AND
AUTOMATION SYSTEMS
The automatic control
system that controls and monitors the HVAC system is called by many names: the
automatic temperature control system (ATC), the energy management and control
system (EMCS), the building automation system (BAS), or the building management
system (BMS).
The control system of choice for major
facilities, and even for some small systems, is a direct digital control (DDC)
system. Most major control system vendors and many of the smaller vendors offer
DDC systems that are similar but contain internal differences. The systems are
computer based and have the ability to communicate within and outside the
system by coded digital signals. System architecture refers to the major
components of the DDC system and their interrelationship. The architecture is
developed by determining what components are initially required, what may be
required in the future, and how the system may expand as additional
requirements are added.
Sequence of Operations
The first element in the
design of the system is the development of a sequence of operation, which is a
written description of the HVAC and related systems operation. A separate
sequence is usually written for each air handling system, describing the
complete operation of the system from control of coils and humidifiers to
control of the room temperature and humidity. Starting and stopping of the air
handling unit fans is outlined, along with interlocking of exhaust or return
fans in relation to the main air system fan operation. Generally all fans
operate at the same time, which is necessary to maintain pressurization. The
sequence also addresses abnormal occurrences such as a smoke detection alarm or
failure of an exhaust fan. The sequence describes what happens to system components during an
abnormal occurrence. It may be necessary to shut a supply fan down if a major
exhaust fan should fail to prevent or minimize the loss of pressurization. The
sequence also describes any energy management strategies to be included in the
system, such as a night temperature setback or reduced ventilation and exhaust
rates during unoccupied periods.
Points List
After the sequence of
operation is completed and the airflow diagrams are defined, the next step is
to develop the alarm, control, and monitoring points list. This is an all
inclusive list of points that are to be connected to the DDC system. There are
two major types of points: digital and analog.
A digital
point is simpler, generally less expensive, and works on a simple on–off or
contact principle. Digital points are used to start and stop fans, indicate an
on–off condition, or anything that requires only a single contact.
An analog point is used to
measure variables such as temperature, pressure, and flow rate. These points
generally use 4- to 20-mA signals that provide varying signals in response to
the parameter measured. The electronic signals
used by the BAS may be transduced from variable pneumatic or pressure signals.
The points list should include analog control points such as cooling coil
valves and room temperatures. Monitoring points can be digital or an analog,
and can include fan run, room temperature indication, damper position, and room
pressure indication.
Alarm points can be either digital or analog
and can include smoke detection in an air handling unit system, high or low
environmental chamber temperature, high room humidity, or loss of room
pressurization.
Estimate of System Cost
The automatic control and
monitoring system is a major cost element in the overall HVAC system for a
pharmaceutical facility. After the points list is developed a good estimate can
be made for the system cost. Several estimating numbers can be used in
providing an educated guess of the cost, with a general range from a low of
$500/point to as high as $1,200/point.
TESTING,
BALANCING, AND CLEANING
For pharmaceutical facilities, establishing
pressure differentials between adjacent spaces is the most critical and is very
tedious to balance. These differentials are obtained by adjusting airflows,
smoke tests, taking pressure readings, and setting controls. This effort can
take some time as each facility is different and each room has different
leakage characteristics that affect pressurization.
As part of the balancing,
you may find that the duct systems or rooms are not as tight as designed and
may require additional sealing to obtain the required pressure differentials.
Recall that airflows shown on drawings are design values and generally require
minor adjustment to achieve the required pressure differentials. A simple
solution to many pressurization problems is to keep increasing outdoor air to
the system. This can lead to problems, if design values are exceeded, with
heating or cooling coils not meeting this need, resulting in off-design room
temperatures and humidity levels. The air handling unit coils will use
available cooling capacity to condition excessive quantities of outdoor air,
resulting in room supply temperature higher than as designed. Therefore, the
best solution first is to tighten the spaces. The optimum time to balance is
when few construction workers or facility personnel are in the spaces. The
balance should be done with all doors closed, since opening and closing results
in system pressure upsets and make balancing difficult.
In general, testing and pre-commissioning
test procedures cover the following parameters:
1. HEPA filter integrity
by DOP testing for pinhole leaks in the filter media, across sealants and frame
gaskets, supporting frame and wall.
2. Air stream velocity
under each filter panel. Airflow measurements should be made at supply, return
and exhaust outlets, as well as traverses across the face of hoods, to verify
proper flows and capture patterns.
3. Establish a spectrum of particulates from appropriate air
samples.
4. Smoke testing for establishing flow patterns if possible and if
required similar test are desirable with the cleanroom in operation and at rest
for a complete validation.
5. Pressure differentials between rooms to passage to change
rooms.
6. Pressure drop across the final filters.
7. Room temperatures and relative humidity. Temperature and
humidity sensors at critical areas should also be checked for accuracy at this
time by actually reading space conditions and checking against values reported
by the BMS.
8. A comprehensive documentation of the testing procedures and
test readings is prepared before the facility is handed over for production.
For
proper evaluation of the facility, the system should be tested while at rest, and during production.
VALIDATION
NO production can start until the cleanroom is validated.
When a pharmaceutical facility is to be validated, the
validating agency will peruse the HVAC documentation and should communicate
with the design engineers to establish the validation protocol as it relates to
the HVAC system. If the design is proper, the system is properly installed, and
the components perform as specified, the systems should be easily validatable.
The validator will follow a master plan and protocols to verify the actual
system installation and operation against design values and intent. The
physical parameters reported by the BMS system shall be verified by
measurements using calibrated instruments to verify accuracy.
DOCUMENTATION
Good manufacturing practices govern the level of control of various parameters for quality assurance, regulating the acceptance criteria, validation of the facility, and documentation for operation and maintenance. The documentation should cover design, operation and performance qualifications of the system.
Design Qualification
The design qualification
document should cover all the following issues:
1. Identification of various systems, their
functions, schematics & flow diagrams, sensors, dampers valves etc.,
critical parameters & fail-safe positions.
2. Layout plans showing various rooms &
spaces and the critical parameters like:
Room
temperature
Room
humidity
Room
pressures and differential pressures between room and room and passages
Process
equipment locations and power inputs
Critical instruments, recorders and alarms, if any
3.Equipment
performance and acceptance criteria for fans, filters, cooling coils, heating
coils, motors & drives.
4.Duct
& pipe layouts showing air inlets, outlets air quantities, water flows and
pressures.
5. Control
schematics and control procedures.
Operation Qualification
This is a commissioning documentation which shall provide
all the details of equipment various points of performance, test readings,
statement of compliance and noncompliance with the acceptance criteria. Broadly
the features are as follows:
1. Installation date showing manufacturers,
model no., ratings of all equipment such as fans, motors, cooling & reheat
coils, filters, HEPA filters, controls etc.
2. As-built drawings showing equipment
layouts, duct and pipe runs, control & fire dampers, settings of various
sensors and controllers.
3. Contractor's rest readings covering
rotation tests, megger readings, air quantities, temperatures and RH pressures
of each space, dry & wet run of controls, air and water balance, HEPA
filter integrity tests at final operating velocities testing of limits &
alarms.
4. Identification of items spaces,
parameters not meeting the acceptance criteria but cannot be corrected.
Performance Qualification
This is essentially for the system operating under full
production conditions and covers among others:
1. Identification of agency for
commissioning, for equipment and instruments and their calibration.
2. Test readings of all
critical parameters under full operating conditions and full production,
modification of readings in the contractors test results, acceptable and
unacceptable departures from design qualification and acceptance criteria.
SUMMARY
HVAC systems in manufacturing portions of
facilities are closely supervised by the FDA and must meet other global current
good manufacturing practices (cGMP’s). Per US GMP, Design and Construction
Features Standard (211.42), sterile area cleanrooms have the following distinct
characteristics:
1. Air should
be of a high microbial quality.
2. Air
handling system is provided with a central HEPA filter bank along with
mandatory terminal filters in order to extend the life of terminal filters.
3. The
filtration regime is generally three stages with two stages of pre-filters, 10
micron (EU 4), 3 micron (EU 8) and one central final filter 0.3 micron (EU 12)
along with terminal HEPA filter.
4. All
sterile critical operations shall be in a laminar flow work station.
5.
Critical areas should have a positive pressure differential relative to
adjacent LESS clean areas: a positive pressure differential of 0.05 inch of
water (12.5 Pa) is acceptable.
6. Supply air outlets are
provided flush at the ceiling level with perforated stainless steel grilles and
terminal absolute filters. Return air grilles to be provided at the floor level
with a return air riser for better scavenging
7.
Walls, floors, and ceilings for cGMP areas are to be constructed of smooth,
cleanable surfaces, impervious to sanitizing solutions and resistant to
chipping, flaking, and oxidizing.
Maintaining proper pressurization gradient
between adjacent spaces is important to prevent infiltration and
cross-contamination. Air filtration techniques and air conditioning components
shall be constantly monitored and upgraded in order to improve the finished
product and reduce energy consumption. Remember, overstating quality
requirements and tolerances may result in unnecessary costs. Higher air flows
and pressures require more HVAC capacity. Since most engineering decisions will
have an impact on HVAC systems, it is important to recognize opportunities to
seek the best engineering solutions.
0 comments:
Post a Comment