PLC - DC INPUTS
Let's now take a look at
how the input circuits of a plc work. This will give us a better understanding
of how we should wire them up. Bad things can happen if we wire them up
incorrectly!
Typically, dc
input modules are available that will work with 5, 12, 24, and 48 volts. Be
sure to purchase the one that fits your needs based upon the input devices you
will use.
We'll first
look at how the dc inputs work. DC input modules allow us to connect either PNP
(sourcing) or NPN (sinking) transistor type devices to them. If we are using a
regular switch (i.e. toggle or pushbutton, etc.) we typically don't have to
worry about whether we wire it as NPN or PNP. We should note that most PLCs
won't let us mix NPN and PNP devices on the same module. When we are using a
sensor (photo-eye, prox, etc.) we do, however, have to worry about its output
configuration. Always
verify whether it's PNP or NPN. (Check with the manufacturer
when unsure)
The
difference between the two types is whether the load (in our case, the plc is
the load) is switched to ground or positive voltage. An NPN type sensor has
the load switched to ground whereas a PNP device has the load switched to
positive voltage.
Below is what
the outputs look like for NPN and PNP sensors.
On the NPN
sensor we connect one output to the PLCs input and the other output to the
power supply ground. If the sensor is not powered from the same supply as the
plc, we should connect both grounds together. NPN sensors are most commonly
used in North America .
Many engineers
will say that PNP is better (i.e. safer) because the load is switched to
ground, but whatever works for you is best. Just remember to plan for the
worst.
On the PNP
sensor we connect one output to positive voltage and the other output to the
PLCs input. If the sensor is not powered from the same supply as the plc, we
should connect both V+'s together. PNP sensors are most commonly used in Europe .
Inside the
sensor, the transistor is just acting as a switch. The sensors internal circuit
tells the output transistor to turn on when a target is present. The transistor
then closes the circuit between the 2 connections shown above. (V+ and plc
input).
The only
things accessible to the user are the terminals labeled COMMON, INPUT 0000,
INPUT 0001, INPUTxxxx... The common terminal either gets connected to V+ or
ground. Where it's connected depends upon the type of sensor used. When using
an NPN sensor this terminal is connected to V+. When using a PNP sensor this
terminal is connected to 0V (ground).
A common
switch (i.e. limit switch, pushbutton, toggle, etc.) would be connected to the
inputs in a similar fashion. One side of the switch would be connected directly
to V+. The other end goes to the plc input terminal. This assumes the common
terminal is connected to 0V (ground). If the common is connected to V+ then
simply connect one end of the switch to 0V (ground) and the other end to the
plc input terminal.
The photocouplers are used to isolate the PLCs internal
circuit from the inputs. This eliminates the chance of any electrical noise
entering the internal circuitry. They work by converting the electrical input
signal to light and then by converting the light back to an electrical signal
to be processed by the internal circuit.