Fail-safe design
Logic
circuits, whether comprised of electromechanical relays or solid-state gates,
can be built in many different ways to perform the same functions. There is
usually no one "correct" way to design a complex logic circuit, but
there are usually ways that are better than others.
In control
systems, safety is (or at least should be) an important design priority. If
there are multiple ways in which a digital control circuit can be designed to
perform a task, and one of those ways happens to hold certain advantages in
safety over the others, then that design is the better one to choose.
Let's take a
look at a simple system and consider how it might be implemented in relay
logic. Suppose that a large laboratory or industrial building is to be equipped
with a fire alarm system, activated by any one of several latching switches
installed throughout the facility. The system should work so that the alarm
siren will energize if any one of the switches is actuated. At first glance it
seems as though the relay logic should be incredibly simple: just use
normally-open switch contacts and connect them all in parallel with each other:
Essentially,
this is the OR logic function implemented with four switch inputs. We could
expand this circuit to include any number of switch inputs, each new switch
being added to the parallel network, but I'll limit it to four in this example
to keep things simple. At any rate, it is an elementary system and there seems
to be little possibility of trouble.
Except in the
event of a wiring failure, that is. The nature of electric circuits is such
that "open" failures (open switch contacts, broken wire connections,
open relay coils, blown fuses, etc.) are statistically more likely to occur
than any other type of failure. With that in mind, it makes sense to engineer a
circuit to be as tolerant as possible to such a failure. Let's suppose that a
wire connection for Switch #2 were to fail open:
If this
failure were to occur, the result would be that Switch #2 would no longer
energize the siren if actuated. This, obviously, is not good in a fire alarm
system. Unless the system were regularly tested (a good idea anyway), no one
would know there was a problem until someone tried to use that switch in an
emergency.
What if the
system were re-engineered so as to sound the alarm in the event of an open
failure? That way, a failure in the wiring would result in a false alarm, a
scenario much more preferable than that of having a switch silently fail and
not function when needed. In order to achieve this design goal, we would have
to re-wire the switches so that an open contact sounded the alarm,
rather than a closed contact. That being the case, the switches will
have to be normally-closed and in series with each other, powering a relay coil
which then activates a normally-closed contact for the siren:
When all
switches are un actuated (the regular operating state of this system), relay CR1
will be energized, thus keeping contact CR1 open, preventing the
siren from being powered. However, if any of the switches are actuated, relay
CR1 will de-energize, closing contact CR1 and sounding
the alarm. Also, if there is a break in the wiring anywhere in the top rung of
the circuit, the alarm will sound. When it is discovered that the alarm is
false, the workers in the facility will know that something failed in the alarm
system and that it needs to be repaired.
Granted, the
circuit is more complex than it was before the addition of the control relay,
and the system could still fail in the "silent" mode with a broken
connection in the bottom rung, but it's still a safer design than the original
circuit, and thus preferable from the standpoint of safety.
This design of
circuit is referred to as fail-safe, due to its intended design to
default to the safest mode in the event of a common failure such as a broken
connection in the switch wiring. Fail-safe design always starts with an
assumption as to the most likely kind of wiring or component failure, and then
tries to configure things so that such a failure will cause the circuit to act
in the safest way, the "safest way" being determined by the physical
characteristics of the process.
Take for
example an electrically-actuated (solenoid) valve for turning on cooling water
to a machine. Energizing the solenoid coil will move an armature which then
either opens or closes the valve mechanism, depending on what kind of valve we
specify. A spring will return the valve to its "normal" position when
the solenoid is de-energized. We already know that an open failure in the
wiring or solenoid coil is more likely than a short or any other type of
failure, so we should design this system to be in its safest mode with the
solenoid de-energized.
If it's
cooling water we're controlling with this valve, chances are it is safer to
have the cooling water turn on in the event of a failure than to shut off, the
consequences of a machine running without coolant usually being severe. This
means we should specify a valve that turns on (opens up) when de-energized and
turns off (closes down) when energized. This may seem "backwards" to
have the valve set up this way, but it will make for a safer system in the end.
One
interesting application of fail-safe design is in the power generation and
distribution industry, where large circuit breakers need to be opened and
closed by electrical control signals from protective relays. If a 50/51 relay
(instantaneous and time over current) is going to command a circuit breaker to
trip (open) in the event of excessive current, should we design it so that the
relay closes a switch contact to send a "trip" signal to the
breaker, or opens a switch contact to interrupt a regularly
"on" signal to initiate a breaker trip? We know that an open
connection will be the most likely to occur, but what is the safest state of
the system: breaker open or breaker closed?
At first, it
would seem that it would be safer to have a large circuit breaker trip (open up
and shut off power) in the event of an open fault in the protective relay
control circuit, just like we had the fire alarm system default to an alarm
state with any switch or wiring failure. However, things are not so simple in
the world of high power. To have a large circuit breaker indiscriminately trip
open is no small matter, especially when customers are depending on the
continued supply of electric power to supply hospitals, telecommunications
systems, water treatment systems, and other important infrastructures. For this
reason, power system engineers have generally agreed to design protective relay
circuits to output a closed contact signal (power applied) to open large
circuit breakers, meaning that any open failure in the control wiring will go
unnoticed, simply leaving the breaker in the status quo position.
Is this an
ideal situation? Of course not. If a protective relay detects an overcurrent
condition while the control wiring is failed open, it will not be able to trip
open the circuit breaker. Like the first fire alarm system design, the
"silent" failure will be evident only when the system is needed.
However, to engineer the control circuitry the other way -- so that any open
failure would immediately shut the circuit breaker off, potentially blacking
out large potions of the power grid -- really isn't a better alternative.
An entire book
could be written on the principles and practices of good fail-safe system
design. At least here, you know a couple of the fundamentals: that wiring tends
to fail open more often than shorted, and that an electrical control system's
(open) failure mode should be such that it indicates and/or actuates the
real-life process in the safest alternative mode. These fundamental principles
extend to non-electrical systems as well: identify the most common mode of
failure, then engineer the system so that the probable failure mode places the
system in the safest condition.
- REVIEW:
- The goal of fail-safe design is to
make a control system as tolerant as possible to likely wiring or
component failures.
- The most common type of wiring and
component failure is an "open" circuit, or broken connection.
Therefore, a fail-safe system should be designed to default to its safest
mode of operation in the case of an open circuit.
0 comments:
Post a Comment